Mersen fuses for the protection of transformers and distribution lines deliver overloadand short circuit protection. These current-limiting fuses will melt at current that canbe as low as 1.7 times the fuse current ratings up to its maximum interrupting rating.These fuses are designed to withstand the transformer magnetizing inrush current.They have 2 (size C), 3 (size D) and 4 (size E) inch diameter barrels with ferrules andare mounted in spring reinforced clips
Features/Benefits:
• Amp-Trap CS-3 and 9F62 series are UL listed for compatibility with UL listed
equipment.
• Ferrule mounting for standard clips and interchangeability with other brands of fuses.
• Current-limiting for superior equipment protection.
• Non-venting for silent operation
• Metal embossed catalog number and manufacturing date for lasting identification.
• Outdoor usage for the 9F62 and 9F60 type EJO.
• Blown-fuse indicator to give positive identification of open fuse:
• Amp-Trap: 2” Barrel 1 lb tripped force - 0.19 Inch
• Amp-Trap: 3” Barrel 2 lb tripped force - 0.50 Inch
• 9F60/9F62: 0.125 lb tripped force – 0.20 Inch
愛澤工業(IZE INDUSTRIES)*經銷、常用備件型號:
MERSEN熔斷器9F60 Series Type EJ-1: (Indoors or outdoors in a weatherproof enclosure)
9F60: 2.75kV – AC: 1E to 200E – 47kA to 52kA IR Sym
9F60: 5.5kV – AC: 0.5E to 25E – 63kA IR Sym
9F60: 15.5kV – AC: 2E to 175E – 31kA to 82kA IR Sym